(Mobilecool indoor) Telecommunication Base Station Special Air Conditioner(Shelter cooling)
1 .Why the base station special air conditioner should be used,
please refer to the table below:
Comparison item | Base station special air conditioner | Normal comfortable air conditioner |
Main service object | Electronic equipment of base station | People |
Main design goal | Control the temperature and cleanness in base station; keep the facilities of base station working smoothly. | To have a comfort temperature range for people inside a room. |
Running cost | Better energy saving performance, low running cost | Worse energy saving performance, higher running cost |
Service cost | Higher reliability, wider working range, lower service charge | Lower reliability, smaller working range, higher service charge |
Reliability for continuously working | Can be working reliability within wide temperature and humidity range, voltage range, | The reliability gets worse and cooling capacity gets smaller if working at high and low temperature. The voltage range is also smaller. |
Service life | Greater than 10 years | Around 2~5 years |
Sensible heat ratio | ≥85% | <70% |
Temperature control accuracy | ±1°C | ±3°C |
Protection and alarm | Full protection and alarm | Less protection and alarm |
Lead-lag control | Yes, standard | Yes, Optional |
Condensing pressure control | Yes | No. |
Free cooling | Yes | No |
Ambient temperature range-Outdoor side | -30°C~50°C | 5°C~43°C |
Ambient temperature range-indoor side | 16°C~35°C | 20°C~30°C |
Remote control and monitoring | Yes | No. |
2.Application
Telecommunication base station
Switching room
Battery station
Power distribution station
Railway signal base station
3. Advantages
Good structure design The unit is designed to be installed universally. It is not needed to make a distinction between left and right hand installation when it is to be adjacent installed at the end of shelter base station. |
The main components such as: compressor, fan, motor, damper and other related components can be accessed in front of the unit and can be field replaced without removing the units when installed side-by-side on the same end of shelter. |
Dual cooling source( MOBILECOOL-SPLIT excluded) Each unit is equipped with both mechanical cooling system and free cooling system as standard. The fresh air free cooling is designed to be the primary source of cooling. |
Anti corrosion All unit framework is provided with corrosion protection treatment. The treatment is sufficient to provide a protection for 15 years life cycle for inland installation. If necessary, the treatment for sea air environment can be supplied as optional. |
High sensible heat ratio The Sensible heat ratio of all the units are high than 0.9 |
Wide working range The unit can work at minimum -15°C(-22°F), maximum 52°C(125.6°F) ambient temperature continuously and reliably. |
High capacity air filter When the pressure drop of the filter reached 250Pa end resistance, the unit air flow will not be less than 90% of air flow at standard condition. |
High torque and low leakage air damper The air filter is equipped with a high torque and low leakage air damper. The time for opening and closing the damper is less than 90 seconds. The Air Leakage across damper is less than 5% by volume of the air normally passing through the unit when a reverse pressure of 125 Pa is applied to the damper |
Smaller dimensions The unit has a smaller dimension because of compact optimized structure design. Its volume is the smallest among the products with similar performance of other suppliers. |
Auto changeover of working mode The unit automatically selects the working mode: mechanic cooling or free cooling according to the temperature of indoor side and outdoor side. In the event of either electrical or mechanical failure affecting the refrigeration system, the unit will be capable of automatic reversion to the fresh air cooling mode. |
Random restart when power recovered After a power failure, when the power is recovered, the unit will restarts automatically with a random time delay between 1 to 60 seconds to avoid many equipments started at the same time. |
Automatic self-diagnosis All the components connected to microprocessor are continuously tested. In case of malfunction, the failure is shown on the display with information accordingly. |
The Attend Mode function When service people is working in base station, he can simply press 2 buttons on the controller interface, then the control temperature of the air conditioner will be set as 22°C(71.6°F) (settable) automatically. Half an hour later (settable), the control temperature of air conditioner will be returned to original set point. |
4 levels password protection There are 4 levels password protection for the control system |
Voltage protection There is a voltage relay for protection. When the supply voltage is out of permitted range, the unit will be stopped. For 3 phase unit, if there is phase unbalance or phase absence, the unit will also be stopped for protection. |
2 types alarm There are a lot of alarms for the complete protection to the unit |
Night storage cooling The customer can enable or disable the control function according to actual situation. If this function is enabled, the control temperature will be reduced when it is running on night time between 18-00hrs and 06-00hrs. So, some cooling capacity can be stored by the low cooling air at night and then be used for day running. |
Humidity limitation The control function can be enabled or disabled on site. If it is enabled, and the humidity of outside is high than 90%, free cooling will be turned off in order to avoid outside humid air introduced to inside of base station. |
Automatic maintenance test A maintenance test facility is provided to enable an engineer to press/select one button that will activate a self-test routine. The self-test routine will check for the satisfactory operation of the fresh air damper and the compressor refrigerant circuits. |
Free cooling |
Ifthe temperature of outdoor temperature is 2 °C or more lower than indoor temperature, the free cooling will be started up to introduce the outdoor air and the indoor air is displace to outdoor, so the indoor air is cooled by outdoor air. |
High efficiency EC fan (Optional) |
EC fan is featured with high efficiency, wide speed adjustment range, low noise, light weight and over 10 years running time continuously. |
High efficiency compressor |
Compressor is the key component of cooling. We use high efficiency compressor to have a basic energy saving. |
Displacement air supply |
Cold air is supplied at low level. The air gets heat at low level and is displaced to high level. So, the inlet air of air conditioner can be higher and the air temperature difference between inlet and outlet can be bigger, which means the air flow rate of the unit can be reduced and at the same time, the energy consumption of supply fan is reduced. Comparing with up flow air distribution, displacement air distribution can save 2~5% energy. |
High indoor control temperature |
The temperature in base station is normally controlled at 24 ±°C. Now, more and more operators is to control the temperature at 28,32 or 35°C. The energy efficiency is getting higher as the temperature goes up, and also the heat dissipated to outside through wall of base station. Totally 10~20% energy saving can be achieved by this way and the unit life cycle can be extended. |
(Mobilecool indoor) Telecommunication Base Station Special Air Conditioner(Shelter cooling)