AIRSYS Refrigeration Engineering Technology (Beijing) Co., Ltd.
Products
Contact Us
  • Contact Person : Ms. gao yuting
  • Company Name : AIRSYS Refrigeration Engineering Technology (Beijing) Co., Ltd.
  • Tel : 86-10-68656161
  • Fax : 86-10-68652453
  • Address : Beijing,Beijing,No.28 LuGu East Street,Shijingshan District,Beijing,China
  • Country/Region : China
  • Zip : 100040

(LHX30) Rack installed air conditioner

(LHX30) Rack installed air conditioner
Product Detailed
Related Categories:Industrial Air Conditioners
LHX 30 a cooling unit for rack series. A rack installed air-conditioiner with cooling capacity in between 20 and 40kW.

1.Working range

                   Room air temperature

                          Room air humidity

+14ºC min. temperature with wet bulb.

+16ºC min. temperature with dry bulb.

+24ºC max. temperature with wet bulb.

+40ºC max. temperature with dry bulb.

20%RH minimum relative humidity.

75%RH maximum relative humidity.

2. Application 

LHX 30 is developed for rack cooling.

3.Advantages 

Compact design to fit into a 1000mm depth standard 42U rack, >30kW cooling capacity.

Easy installation with symmetrical design for either left or right air flow.

Easy maintenance with modular fan unit, plug and play, interchangeable.

Microprocessor control system

Remote monitoring via RS485/232

Precise control with variable speed fan and proportional controlled valves.

Water pipe connection both vertical and horizontal.

4.Main components

Main Components

Unit Base, panels and frame

The material of base, panels and frame are galvanized steel. The fan module and front panel will be painted with plastic powder. Color can be selected.

Copper pipe connection

Fan

DC driven Axial fan, variable speed control.

Air filter

Nylon air filter with aluminum structure

Electric board

In a separate compartment.

Heat exchanger coil

3 way valve (or 2 way valve) with actuator

Water pipe connection couple

Controller

Programmable microprocessor, equipped with supply air and return air temperature sensor, and inlet water temperature sensor. RS485/232 interface is optional.

Display

Can be LED or LCD.

5.Unit Specification

Parameters

Unit

Default

Cooling Capacity

kW

32.0

Sensible cooling capacity

kW

32.0

Cooling medium

Water

Water flow volume

m³/h

5.7

Unit dimensions and Weight

Width

mm

189

Depth

mm

850

Height

mm

1849

Weight

kg

102

Unit test conditions:

Air inlet temp. : 43ºC; Wet bulb temp. :23.5ºC

Water inlet temp.:8ºC; water outlet temp.:13ºC

(LHX30) Rack installed air conditioner



Copyright Notice @ 2008-2022 ECBAY Limited and/or its subsidiaries and licensors. All rights reserved.