(Datacool7E1C1) computer room air conditioner

(Datacool7E1C1) computer room air conditioner
Product Detailed
Related Categories:Industrial Air Conditioners
1Energy Saving and High Efficiency 2Various Air flow pattern 3Pretty and Compact 4Safety and Reliability

Model:7E1D1~30E1D3

Temperature control range:-30°Cto 50°C

Humidity control range:35%~80%±5%

Air flow:2475~6565 m3/h

1.Application

ICT industry

Small to mid-size switching room for telecommunication

The pagers and SMS treatment center

Microwave and satellite station

Mobile telecommunications center

Small to mid-size data center and computer room

Network control center

UPS and battery room

Hot spots in large data center

CT and MRI room

Medical testing room

Industrial process control center

High-precision environment and laboratory

Standard testing and calibration center

Precision machining room

Museum and archive room

2.Advantages

2.1 Energy Saving and High Efficiency

Energy saving and high efficiency is the core value of DATACOOL products. Selecting high efficiency components and designing special delay control logic to improve working efficiency.Besides there are 2 running modes available, i.e.: standard running mode and energy saving running mode is alternative. The condensing fan speed is controlled to make the high pressure of refrigeration system within a better range, this saves not only the energy consumption of fan running but also the power consumption of refrigeration system.

2.2 Various Air Flow Pattern

There are 3 kinds of air flow patterns (over flow, under flow, displacement flow), so, the customer is easy to design a best air distribution according to the computer room layout.

2.3 Low Noise and Less Dust

Optional parts are properly selected for DATACOOL series, such as insulation and soundproofing material, quieter cover of compressor, rubber shock holders of raised floor with height adjusting. All above methods can make noise reduction to 5~10dB (A).

The G4 air filter used for DATACOOL series is made of synthetic washable fiber. 80% of 5 μ dust and 20% of 1 μ dust will be filtered by it. It can fully meet the requirements of the cleanness of the indoor air.

2.4 Pretty and Compact

Main parts of DATACOOL series, including panels, bases and frameworks are painted in black, which is very close to the color of the racks. In addition, the height and the depth of the unit are similar to the standard racks. It is nice-looking as its design style matches the devices style inside the computer rooms.

Because of its merits, such as compact structure, small floor space, low weight, DATACOOL is easy to be moved and installed, even in narrow space.

2.5 Safety and Reliability

To guarantee high reliability, compressors, fans, condensers, evaporators, expansion valves and other key components are selected from international famous brands, in accordance with major international industrial standards.

2.6 Intelligent Control

All the components such as compressors, fans, heaters, and humidifier are intelligently controlled and protected by microprocessor.

 

Comparison between DATACOOL and Normal comfort AC

 

Comparison topic

            DATACOOL

       Normal comfort AC

Product design goal

Build up a high precision temperature and humidity control for the electronic equipment, and give a clean air environment for these equipments, meet the higher requirements of temperature, humidity, purity and reliability from equipment.

Supply a comfortable air environment for the people inside office or residential room.

Meet the comfortable requirement of temperature of people inside the room or office.

Main service object

Electronic equipment or precision instruments

People

Air circulation volume

Lower enthalpy difference and bigger air circulation volume with circulation times 30-50 per hour, which benefits to the handling of air with high sensible heat.

Big enthalpy difference and small air circulation volume with circulation time 5-10 times per hour, which does not benefit to the handling of air with high sensible heat.

Basic function

Control both the temperature and humidity

Only control temperature, cannot control humidity

Energy efficiency

≥2.9

≤2.6

Sensible heat

Higher,>0.90

Lower, 0.6~0.7

Supply temperature

Higher, less water condensation

Lower, easily water condensation

Service working amount

Less

More

Working life(At the condition of computer room)

>15 years

2~4 years

Initial cost

High

Low

Total cost ownership

Low

High

Remark:

Obviously from the above table, it is not correct to select normal comfortable air conditioner for the reason of saving initial cost.

DATACOOL Energy saving calculation and comparison 

Comparison condition

 

DATACOOL

Normal AC

Product type

 

Precision

Normal

Unit size

 

5HP

5HP

Unit cooling capacity

kW

13.3

12.8

EER

 

2.95

2.69

Power consumption of refrigeration system

kW

4.51

4.76

Sensible heat ratio

 

0.93

0.75

Average power consumption of facilities in computer room

kW

8.5

8.5

Calculation result

   

Working hours of AC unit

 

6020

7756

Total annual heat load from facilities in computer room

kW.h

74460

74460

Total annual heat load of humidifier (i.e.: total power consumption of humidifier)

kW.h

5605

24820

Total annual heat load of computer room (electronic equipment + humidifier)

kW.h

80065

99280

Total annual power consumption of AC unit (Refrigeration + humidification)

kW

32745

61727

Annual power saving of DATACOOL unit

kW.h

28982

Annual working hours ratio of AC unit

 

69%

89%

Remark:The above calculation is based on a 30 m2 computer room with 8.5 kW average heat load of equipment. It can be found that the DATACOOL units can save a big amount energy with up to 47% energy saving.

3.Unit Specification

Indoor unit parameter

Unit size

 

7E1C1

Cooling capacity

  

Total(*)

kW

7.6

Sensible(*)

kW

7.2

Compressor

  

Supply fan

  

Qty.

n.

1

Air flow

m3/h

2450

Model

 

CMD4

Weight

kg

142

(Datacool7E1C1) computer room air conditioner